No. Warren Controls specifies the ARIA as a linear electric actuator engineered specifically for its rising stem control valves. Compatibility with third-party equipment should not be assumed; the mechanical interface, thrust output, and stroke length must be verified by our technical team.
Stroke up to 1.3125 in.
IP67 · NEMA 4X
ARIA: Fast electric modulation with fail-safe capabilities based on configuration
The ARIA actuator integrates a brushless DC (BLDC) electric motor, a linear transmission, and a 12-bit Hall-effect position sensor. Engineered specifically for Warren Controls rising-stem control valves, it is available with various valve body configurations and control modes. Optimal selection requires evaluating thrust, stroke length, differential pressure, and the valve's specific hydraulic service.
Linear Motion
Rated thrust of 450 lbf and linear speed of approximately 2 mm/s (12 seconds per inch). The actuator's maximum stroke is rated at 1.3125 in. per the product specifications.
Positioning and Control
12-bit Hall effect sensor, analogue current or voltage signals, and control settings. The feedback type depends on the selected configuration.
Fail-Safe on Power Loss
Depending on the model, spring-return to open or closed position, or fail-in-place operation. The fail-safe direction must be specified and validated for your application.
Industrial Protection
Featuring an IP67 / NEMA 4X enclosure and a BLDC motor, the brochure highlights an actuator engineered for over 1.5 million cycles, subject to standard operating and maintenance conditions.
Four Warren Controls ARIA control valve assemblies
Four valve-actuator assemblies are available: ARA for flanged mixing, ARB for NPT connections, ARC for large cast-iron configurations, and ARD for two-way cage-guided control.
3-WAY MIXING · FLANGED
ARIA ARA
Three-way mixing valve engineered with a cast steel WCB or stainless steel CF8M body. Designed to combine two separate flows into a single outlet, ideal for hot water systems and thermal loops.
Function
3-Way Mixing
Diameters
½ to 2 in
End Connection
Class 150/300 Flanges
Materials
WCB or CF8M
The ARA is engineered for three-way mixing service. Due to its ARIA configuration, it cannot be converted into a diverting valve simply by reversing the flow direction.
SMALL PIPING SYSTEMS · NPT
ARIA ARB
Two-way or three-way assemblies with NPT connections, featuring bronze or stainless steel bodies depending on the configuration. Engineered for modulating, mixing, or diverting applications.
Function
2-way or 3-way
Diameters
½ to 2 in
End Connection
NPT Threaded
Materials
Bronze / Stainless Steel
Two-way and three-way configurations are available with a variety of packing options. Seat materials are selected based on the process fluid and operating temperature.
LARGE DIAMETER · CAST IRON
ARIA ARC
This flanged cast iron line meets higher flow capacity requirements on compatible systems, offering a selection of trim options tailored to your specific hydraulic application.
Function
2-way or 3-way
Diameters
2½ to 6 in.
End Connection
Class 125/250 Flanges
Body
Cast Iron
For hydronic systems and higher flow rates, port size and actuator selection depend on the effective flow range.
TWO-WAY · STEEL
ARIA ARD
Two-way cage-guided valve available with a WCB carbon steel or CF8M stainless steel body. Designed for control and low-flow configurations on small lines, featuring application-specific trim selection.
Function
2-way
Diameters
½ to 2 in
End Connection
Class 150/300 Flanges
Body
WCB / CF8M
Steam, utilities, and process fluids, based on selected materials, pressure class, Cv, and packing or seals.
Selecting the Right ARIA Actuator and Valve Solution
ARIA is engineered specifically for Warren Controls rising stem valves, not as a universal retrofit actuator. Proper selection requires verifying the valve body, thrust, stroke, electrical specifications, fail-safe direction, and installation requirements.
MECHANICAL AND HYDRAULIC SYSTEMS
Valve Type and Function
Identify ARA, ARB, ARC, or ARD, the number of ports, flow direction, and mixing, diverting, or modulating function.
Thrust and Stroke
The ARIA actuator is rated at 450 lbf, with a maximum stroke of 1.3125 in; shut-off capability and travel must be verified at the process ΔP.
Mounting Interface
Inspect the bracket, stem coupling, pillars, clearances, and mounting orientation. Do not assume direct fitment with other brands.
ELECTRICAL AND SAFETY
Control signal
0–20 / 4–20 mA or 0–10 / 2–10 V input signals. Split-range operation and direct or reverse action are fully documented.
Supply Voltage
24 VAC/VDC in the standard configuration; a wide-range 100–240 VAC power supply is available as an option.
Fail-safe position
Specify open, closed, or fail-in-place (stayput) depending on the configuration. Fail modes are not interchangeable without verifying the part number.
To consult with Warren Controls: specify the media, operating pressures, flow rates, temperature, supply voltage, control signal, fail-safe position, and mounting geometry.
Where Can ARIA Electric Actuation and Control Be Deployed?
Suitability depends on the valve body model, not the actuator alone. Here are control applications to evaluate against the technical documentation for each configuration.
How Does the ARIA Electric Actuator Operate?
The brushless electric motor drives a stem via mechanical transmission, with position monitoring ensured by a 12-bit Hall effect sensor. The ARIA features control adjustments, analog monitoring functions, and a spring-return fail-safe architecture on corresponding variants. Overall assembly limits depend on the specific valve configuration and operating environment.
12-bit Hall-effect sensor
Non-contact stem position measurement and stroke control for modulating applications, featuring a configurable control range.
12 seconds per inch
Rated stroke speed of 2 mm/s as specified in the technical documentation. Actual travel time must be evaluated based on valve stroke length and specific system configuration.
DIP Switch and Push-Button Settings
Direct or reverse acting, split-range, and recalibration capabilities available based on selected functions. Installation and commissioning procedures must adhere to manufacturer guidelines.
Required operating specifications for your ARIA
This industrial electrical equipment features options that should not be considered standard across every configuration.
SAFETY & SECURITY
Safety spring
Fail-open and fail-close configurations upon loss of power or signal; fail-in-place versions are also specified by the manufacturer.
SIGNAL
Analog Control
0/4–20 mA and 0/2–10 V inputs, position feedback, and split-range capability based on specified configuration.
POWER SUPPLY
24 V and wide-range option
Standard 24 VAC/DC, with optional 100–240 VAC power supply; select according to site electrical equipment.
ENVELOPE
IP67 / NEMA 4X
Protective housing and ½" NPT connections. Ambient temperature range rated from -20 to +60°C per the technical brochure; verify on-site installation conditions.
Plan an ARIA Project or Valve Replacement
ARIA is engineered as an integrated valve-actuator assembly. To prepare a quote request, please gather the hydraulic function, min/normal/max flow rates, upstream/downstream pressures, media, end connections, supply voltage, and fail-safe logic. For existing installations, please include a photo of the nameplate and the dimensional drawing.
OPERATION
Understanding ARIA
The manufacturer's overview document details the BLDC motor, stroke, feedback signals, spring-return mechanism, and control options, supporting your application qualification process.
VALVE SELECTION
Verify Configuration
Data sheets ARA, ARB, ARC, and ARD outline the dimensions, materials, Cv ratings, shut-off leakage classes, and flow restrictions specific to each valve body.
REPLACEMENT
Legacy AmurAct Actuator
A legacy AmurAct actuator or assembly should not be deemed interchangeable without first verifying the stroke, valve, connection, and control interface. Our local technical experts can engineer a tailored ARIA solution for your application.
THE ADVANTAGES OF VAMECA
Whether for a new installation or the replacement of existing equipment, VAMECA provides the technical expertise to define your process parameters accurately before consulting Warren Controls.
FAQ
Compatibility, fail-safe spring return, analog control, ARA to ARD models, and replacement options.
Your Dedicated Source for ARIA Actuators in Canada
VAMECA supports maintenance, engineering, and procurement teams across Quebec and Canada in specifying ARIA control valves or drop-in replacements. Leveraging our technical expertise, we clarify engineering specifications, review official documentation, and deliver reliable, accurate quotes tailored to your actual operating conditions.
Valve and Actuator Selection
We evaluate the selection between ARA, ARB, ARC, and ARD models, the number of ports, materials of construction, dimensions, and the required operating torque.
Customized electric actuation
From analogue inputs and feedback to power supply, safety logic, and mounting: we thoroughly evaluate your control requirements and available interfaces.
Technical Documentation & Request a Quote